GeneratorOperatingModeEnum
Selector mode of the generator set control panel.
GEN-GeneratorSet
i=29
ns=1;i=3901
Control is off; the set will not start automatically or manually.Manual/hand mode; the set runs on operator command.Automatic mode; the set starts/stops on remote or utility-failure signals.Test mode; a commanded test run, optionally with load.Scheduled exercise/self-test run.Started by a remote start signal.Maintenance/service mode; starting is inhibited or restricted.Locked out; starting is blocked until reset.
EnumStrings
i=68
ns=1;i=3001
OffManualAutoTestExerciseRemoteStartMaintenanceLockout
FuelTypeEnum
Primary fuel of the generator set.
GEN-GeneratorSet
i=29
ns=1;i=3902
EnumStrings
i=68
ns=1;i=3002
DieselNaturalGasPropaneLPGGasolineBiFuelDualFuelBiodieselHVORenewableDieselHydrogenBiogasLandfillGasFieldGasSyngasOther
GeneratorApplicationRatingEnum
Application/duty rating per ISO 8528 plus the data-center-continuous rating.
GEN-GeneratorSet
i=29
ns=1;i=3903
ESP: standby power at variable load, limited hours, no overload.PRP: unlimited hours at variable load, typically 10% overload 1h/12h.COP: unlimited hours at constant load, no overload.LTP: limited hours per year at defined load.DCC: continuous operation for data-center loads.
EnumStrings
i=68
ns=1;i=3003
EmergencyStandbyPrimeContinuousLimitedTimeDataCenterContinuous
ElectricalConnectionEnum
Winding/connection configuration of the alternator output.
GEN-GeneratorSet
i=29
ns=1;i=3904
EnumStrings
i=68
ns=1;i=3004
UnknownWyeWyeSolidlyGroundedWyeResistanceGroundedWyeUngroundedDeltaOpenDeltaZigZagSinglePhaseThreeWire
ExcitationTypeEnum
Excitation method of the alternator.
GEN-GeneratorSet
i=29
ns=1;i=3905
Permanent Magnet Generator - independent excitation supply.
EnumStrings
i=68
ns=1;i=3005
UnknownShuntPMGAREPAuxiliaryWindingStaticExciter
CoolingMethodEnum
Primary cooling method of the engine.
GEN-GeneratorSet
i=29
ns=1;i=3906
EnumStrings
i=68
ns=1;i=3006
AirCooledLiquidCooled
AspirationEnum
Air induction method of the engine.
GEN-GeneratorSet
i=29
ns=1;i=3907
EnumStrings
i=68
ns=1;i=3007
NaturallyAspiratedTurbochargedTurbochargedAftercooled
EmissionsStandardEnum
Emissions certification standard of the engine.
GEN-GeneratorSet
i=29
ns=1;i=3908
EnumStrings
i=68
ns=1;i=3008
UnregulatedEPATier1EPATier2EPATier3EPATier4InterimEPATier4FinalEUStageIIIEUStageIVEUStageVOther
CanBusStateEnum
State of the engine CAN bus / SAE J1939 network interface.
GEN-GeneratorSet
i=29
ns=1;i=3909
EnumStrings
i=68
ns=1;i=3009
OfflineOnlineErrorWarningErrorPassiveBusOff
TransferSwitchPositionEnum
Contact position of an automatic transfer switch.
GEN-GeneratorSet
i=29
ns=1;i=3910
Connected to Source 1 (normal/utility).Connected to Source 2 (emergency/generator).Center-off / neutral position.
EnumStrings
i=68
ns=1;i=3010
UnknownSource1Source2NeutralInTransitionBypassSource1BypassSource2Isolated
TransferTransitionTypeEnum
Transition method of an automatic transfer switch.
GEN-GeneratorSet
i=29
ns=1;i=3911
Break-before-make.Break-before-make with center-off delay.Make-before-break; momentary paralleling.Ramped, no-break transfer while paralleled.
EnumStrings
i=68
ns=1;i=3011
OpenTransitionDelayedTransitionClosedTransitionSoftLoadTransitionBypassIsolation
AtsOperatingStateEnum
Operating state of an automatic transfer switch.
GEN-GeneratorSet
i=29
ns=1;i=3912
EnumStrings
i=68
ns=1;i=3012
UnknownNormalAvailableEmergencyAvailableNormalConnectedEmergencyConnectedTransferPendingTransferringRetransferPendingExercisingTestFaultedBypassedIsolated
AlarmSeverityEnum
Severity class of a generator protection event.
GEN-GeneratorSet
i=29
ns=1;i=3913
The set continues to run at reduced output.The engine is shut down.The generator breaker is tripped.The set is locked out and requires manual reset.
EnumStrings
i=68
ns=1;i=3013
InfoWarningDerateShutdownElectricalTripLockoutEmergencyStop
GeneratorProtectionFunctionEnum
Protection / fault function that raised a generator alarm.
GEN-GeneratorSet
i=29
ns=1;i=3914
Fail to start within the crank limit.
EnumStrings
i=68
ns=1;i=3014
OtherLowOilPressureHighOilTemperatureHighCoolantTemperatureLowCoolantTemperatureLowCoolantLevelHighCoolantPressureOverspeedUnderspeedOvercrankFailToCrankStarterFailureLowFuelLevelCriticalLowFuelFuelLeakLowFuelPressureHighFuelPressureWaterInFuelFuelFilterRestrictionAirFilterRestrictionHighExhaustTemperatureTurbochargerFaultEcuFaultEngineDerateOvervoltageUndervoltageOverfrequencyUnderfrequencyOverloadOvercurrentShortCircuitGroundFaultPhaseLossPhaseReversalVoltageImbalanceCurrentImbalanceReversePowerLossOfExcitationOverexcitationUnderexcitationAvrFaultHighWindingTemperatureHighBearingTemperatureLowBatteryVoltageHighBatteryVoltageBatteryChargerFailureWeakBatteryControllerFaultCommunicationLostSensorFailureEmergencyStopDefLevelLowDefQualityPoorDpfSootHighRegenerationRequiredAftertreatmentFaultEnclosureHighTemperatureDoorOpenFuelBasinLeakRadiatorFanFailureJacketWaterHeaterFailureAtsFailedToTransferBreakerFailedToCloseSynchronizationFailure
ParallelingSystemStateEnum
Operating state of a paralleling / switchgear system.
GEN-GeneratorSet
i=29
ns=1;i=3915
EnumStrings
i=68
ns=1;i=3015
OffStandbyStartSequenceDeadBusCloseSynchronizingParallelingLoadSharingLoadDemandUtilityParallelPeakShavingBaseLoadLoadShedSoftUnloadCooldownFaultedEmergencyStopMaintenanceBypass
AftertreatmentStateEnum
State of the exhaust aftertreatment system.
GEN-GeneratorSet
i=29
ns=1;i=3916
EnumStrings
i=68
ns=1;i=3016
NotEquippedNormalPassiveRegenActiveRegenRegenInhibitedRegenRequiredDerateActiveFaulted
J1939LampStatusEnum
SAE J1939 DM1 diagnostic lamp status (lamp state plus flash rate).
GEN-GeneratorSet
i=29
ns=1;i=3917
The lamp is off.The lamp is on (steady).The lamp is flashing slowly.The lamp is flashing fast.The lamp status is not available.
EnumStrings
i=68
ns=1;i=3017
OffOnSlowFlashFastFlashNotAvailable
DiagnosticTroubleCodeType
A SAE J1939 diagnostic trouble code (DTC) reported by an engine ECU.
GEN-GeneratorSet
i=22
ns=1;i=6001
ns=1;i=6002
Suspect Parameter Number identifying the faulty subsystem.Failure Mode Identifier describing the type of failure.Number of times the fault has become active.J1939 SPN conversion method flag.TRUE while the fault is currently active (DM1).J1939 source address of the ECU that reported the code.Name of the ECU/controller that reported the code.Severity classification of the fault.Human-readable description of the fault.
Default Binary
i=76
ns=1;i=3050
Default XML
i=76
ns=1;i=3050
GeneratorIdentificationType
Identification and nameplate of a generator set. Extends the Machinery MachineIdentificationType with generator-specific nameplate data.
GEN-Identification
ns=3;i=1012
ns=1;i=6003
ns=1;i=6004
ns=1;i=6005
ns=1;i=6006
ns=1;i=6007
ns=1;i=6008
ns=1;i=6009
ns=1;i=6010
ns=1;i=6011
ns=1;i=6012
ns=1;i=6014
ns=1;i=6016
ns=1;i=6018
ns=1;i=6020
SpecificationNumber
Vendor build/specification code that identifies the exact configuration.
i=80
i=68
ns=1;i=1016
ProductFamily
Vendor product family or series to which the set belongs.
i=80
i=68
ns=1;i=1016
EngineModel
Model designation of the prime-mover engine.
i=80
i=68
ns=1;i=1016
EngineSerialNumber
Serial number of the prime-mover engine.
i=80
i=68
ns=1;i=1016
AlternatorModel
Model designation of the alternator.
i=80
i=68
ns=1;i=1016
AlternatorSerialNumber
Serial number of the alternator.
i=80
i=68
ns=1;i=1016
ControllerModel
Model designation of the control panel.
i=80
i=68
ns=1;i=1016
FuelType
Primary fuel of the set.
i=80
i=68
ns=1;i=1016
EmissionsStandard
Emissions certification standard.
i=80
i=68
ns=1;i=1016
RatedRealPower
Nameplate rated real power. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1016
ns=1;i=6013
EngineeringUnits
i=78
i=68
ns=1;i=6012
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
RatedApparentPower
Nameplate rated apparent power. EngineeringUnits: kVA.
i=80
i=17497
ns=1;i=1016
ns=1;i=6015
EngineeringUnits
i=78
i=68
ns=1;i=6014
i=889http://www.opcfoundation.org/UA/units/un/cefact4937281kV·Akilovolt ampere
RatedVoltage
Nameplate rated line-to-line voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1016
ns=1;i=6017
EngineeringUnits
i=78
i=68
ns=1;i=6016
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
RatedFrequency
Nameplate rated frequency. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1016
ns=1;i=6019
EngineeringUnits
i=78
i=68
ns=1;i=6018
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
SoundRatingAt7m
Sound pressure level at 7 m (23 ft) in dB(A).
i=80
i=68
ns=1;i=1016
GeneratorStateMachineType
Finite state machine describing the operating state of a generator set: Off, Ready, Starting, Warmup, Running, Loaded, Synchronizing, Paralleled, Cooldown, Stopping, Fault and EmergencyStopped.
GEN-StateMachine
i=2771
ns=1;i=6021
ns=1;i=6023
ns=1;i=6025
ns=1;i=6027
ns=1;i=6029
ns=1;i=6031
ns=1;i=6033
ns=1;i=6035
ns=1;i=6037
ns=1;i=6039
ns=1;i=6041
ns=1;i=6043
ns=1;i=6045
ns=1;i=6047
ns=1;i=6049
ns=1;i=6051
ns=1;i=6053
ns=1;i=6055
ns=1;i=6057
ns=1;i=6059
ns=1;i=6061
ns=1;i=6063
ns=1;i=6065
ns=1;i=6067
ns=1;i=6069
ns=1;i=6071
ns=1;i=6073
ns=1;i=6075
ns=1;i=6077
ns=1;i=6079
ns=1;i=6081
ns=1;i=6083
ns=1;i=6085
ns=1;i=6087
ns=1;i=6089
Off
State 'Off' of the generator set operating state machine.
i=2309
ns=1;i=1011
ns=1;i=6022
StateNumber
i=78
i=68
ns=1;i=6021
1
Ready
State 'Ready' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6024
StateNumber
i=78
i=68
ns=1;i=6023
2
Starting
State 'Starting' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6026
StateNumber
i=78
i=68
ns=1;i=6025
3
Warmup
State 'Warmup' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6028
StateNumber
i=78
i=68
ns=1;i=6027
4
Running
State 'Running' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6030
StateNumber
i=78
i=68
ns=1;i=6029
5
Loaded
State 'Loaded' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6032
StateNumber
i=78
i=68
ns=1;i=6031
6
Synchronizing
State 'Synchronizing' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6034
StateNumber
i=78
i=68
ns=1;i=6033
7
Paralleled
State 'Paralleled' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6036
StateNumber
i=78
i=68
ns=1;i=6035
8
Cooldown
State 'Cooldown' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6038
StateNumber
i=78
i=68
ns=1;i=6037
9
Stopping
State 'Stopping' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6040
StateNumber
i=78
i=68
ns=1;i=6039
10
Fault
State 'Fault' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6042
StateNumber
i=78
i=68
ns=1;i=6041
11
EmergencyStopped
State 'EmergencyStopped' of the generator set operating state machine.
i=2307
ns=1;i=1011
ns=1;i=6044
StateNumber
i=78
i=68
ns=1;i=6043
12
OffToReady
Transition 'OffToReady'.
i=2310
ns=1;i=1011
ns=1;i=6021
ns=1;i=6023
ns=1;i=6046
TransitionNumber
i=78
i=68
ns=1;i=6045
1
ReadyToStarting
Transition 'ReadyToStarting'.
i=2310
ns=1;i=1011
ns=1;i=6023
ns=1;i=6025
ns=1;i=6048
TransitionNumber
i=78
i=68
ns=1;i=6047
2
ReadyToOff
Transition 'ReadyToOff'.
i=2310
ns=1;i=1011
ns=1;i=6023
ns=1;i=6021
ns=1;i=6050
TransitionNumber
i=78
i=68
ns=1;i=6049
3
StartingToWarmup
Transition 'StartingToWarmup'.
i=2310
ns=1;i=1011
ns=1;i=6025
ns=1;i=6027
ns=1;i=6052
TransitionNumber
i=78
i=68
ns=1;i=6051
4
StartingToFault
Transition 'StartingToFault'.
i=2310
ns=1;i=1011
ns=1;i=6025
ns=1;i=6041
ns=1;i=6054
TransitionNumber
i=78
i=68
ns=1;i=6053
5
WarmupToRunning
Transition 'WarmupToRunning'.
i=2310
ns=1;i=1011
ns=1;i=6027
ns=1;i=6029
ns=1;i=6056
TransitionNumber
i=78
i=68
ns=1;i=6055
6
RunningToLoaded
Transition 'RunningToLoaded'.
i=2310
ns=1;i=1011
ns=1;i=6029
ns=1;i=6031
ns=1;i=6058
TransitionNumber
i=78
i=68
ns=1;i=6057
7
RunningToSynchronizing
Transition 'RunningToSynchronizing'.
i=2310
ns=1;i=1011
ns=1;i=6029
ns=1;i=6033
ns=1;i=6060
TransitionNumber
i=78
i=68
ns=1;i=6059
8
SynchronizingToParalleled
Transition 'SynchronizingToParalleled'.
i=2310
ns=1;i=1011
ns=1;i=6033
ns=1;i=6035
ns=1;i=6062
TransitionNumber
i=78
i=68
ns=1;i=6061
9
SynchronizingToRunning
Transition 'SynchronizingToRunning'.
i=2310
ns=1;i=1011
ns=1;i=6033
ns=1;i=6029
ns=1;i=6064
TransitionNumber
i=78
i=68
ns=1;i=6063
10
ParalleledToLoaded
Transition 'ParalleledToLoaded'.
i=2310
ns=1;i=1011
ns=1;i=6035
ns=1;i=6031
ns=1;i=6066
TransitionNumber
i=78
i=68
ns=1;i=6065
11
LoadedToCooldown
Transition 'LoadedToCooldown'.
i=2310
ns=1;i=1011
ns=1;i=6031
ns=1;i=6037
ns=1;i=6068
TransitionNumber
i=78
i=68
ns=1;i=6067
12
RunningToCooldown
Transition 'RunningToCooldown'.
i=2310
ns=1;i=1011
ns=1;i=6029
ns=1;i=6037
ns=1;i=6070
TransitionNumber
i=78
i=68
ns=1;i=6069
13
CooldownToStopping
Transition 'CooldownToStopping'.
i=2310
ns=1;i=1011
ns=1;i=6037
ns=1;i=6039
ns=1;i=6072
TransitionNumber
i=78
i=68
ns=1;i=6071
14
StoppingToOff
Transition 'StoppingToOff'.
i=2310
ns=1;i=1011
ns=1;i=6039
ns=1;i=6021
ns=1;i=6074
TransitionNumber
i=78
i=68
ns=1;i=6073
15
RunningToFault
Transition 'RunningToFault'.
i=2310
ns=1;i=1011
ns=1;i=6029
ns=1;i=6041
ns=1;i=6076
TransitionNumber
i=78
i=68
ns=1;i=6075
16
LoadedToFault
Transition 'LoadedToFault'.
i=2310
ns=1;i=1011
ns=1;i=6031
ns=1;i=6041
ns=1;i=6078
TransitionNumber
i=78
i=68
ns=1;i=6077
17
ParalleledToFault
Transition 'ParalleledToFault'.
i=2310
ns=1;i=1011
ns=1;i=6035
ns=1;i=6041
ns=1;i=6080
TransitionNumber
i=78
i=68
ns=1;i=6079
18
FaultToOff
Transition 'FaultToOff'.
i=2310
ns=1;i=1011
ns=1;i=6041
ns=1;i=6021
ns=1;i=6082
TransitionNumber
i=78
i=68
ns=1;i=6081
19
RunningToEmergencyStopped
Transition 'RunningToEmergencyStopped'.
i=2310
ns=1;i=1011
ns=1;i=6029
ns=1;i=6043
ns=1;i=6084
TransitionNumber
i=78
i=68
ns=1;i=6083
20
LoadedToEmergencyStopped
Transition 'LoadedToEmergencyStopped'.
i=2310
ns=1;i=1011
ns=1;i=6031
ns=1;i=6043
ns=1;i=6086
TransitionNumber
i=78
i=68
ns=1;i=6085
21
ParalleledToEmergencyStopped
Transition 'ParalleledToEmergencyStopped'.
i=2310
ns=1;i=1011
ns=1;i=6035
ns=1;i=6043
ns=1;i=6088
TransitionNumber
i=78
i=68
ns=1;i=6087
22
EmergencyStoppedToOff
Transition 'EmergencyStoppedToOff'.
i=2310
ns=1;i=1011
ns=1;i=6043
ns=1;i=6021
ns=1;i=6090
TransitionNumber
i=78
i=68
ns=1;i=6089
23
J1939DiagnosticInterfaceType
The engine CAN bus / SAE J1939 diagnostic interface. Surfaces the network connection parameters, J1939 lamp status and active/previously-active diagnostic trouble codes reported by the engine ECU.
GEN-CANbus
i=58
ns=1;i=6091
ns=1;i=6092
ns=1;i=6093
ns=1;i=6094
ns=1;i=6095
ns=1;i=6096
ns=1;i=6097
ns=1;i=6098
ns=1;i=6099
ns=1;i=6100
ns=1;i=6101
ns=1;i=6102
ProtocolName
Name of the diagnostic protocol, e.g. 'SAE J1939'.
i=78
i=68
ns=1;i=1010
NetworkName
Name/identifier of the CAN network (e.g. CAN0).
i=80
i=68
ns=1;i=1010
SourceAddress
J1939 source address of the engine ECU.
i=80
i=68
ns=1;i=1010
Baudrate
CAN bit rate in bit/s (typically 250000 or 500000).
i=80
i=68
ns=1;i=1010
BusState
State of the CAN bus interface.
i=80
i=63
ns=1;i=1010
AmberWarningLamp
J1939 DM1 amber warning lamp status.
i=80
i=63
ns=1;i=1010
RedStopLamp
J1939 DM1 red stop lamp status.
i=80
i=63
ns=1;i=1010
MalfunctionIndicatorLamp
J1939 DM1 malfunction indicator lamp status.
i=80
i=63
ns=1;i=1010
ProtectLamp
J1939 DM1 protect lamp status.
i=80
i=63
ns=1;i=1010
ActiveDiagnosticTroubleCodes
Currently active DTCs (J1939 DM1).
i=80
i=63
ns=1;i=1010
PreviouslyActiveDiagnosticTroubleCodes
Previously active DTCs (J1939 DM2).
i=80
i=63
ns=1;i=1010
ClearPreviouslyActiveDtcs
Clear previously active diagnostic trouble codes (J1939 DM3/DM11).
i=80
ns=1;i=1010
ExhaustAftertreatmentType
Exhaust aftertreatment subsystem (DPF/SCR/DEF) for Tier 4 / Stage V engines.
GEN-Components
ns=2;i=15063
ns=1;i=6103
ns=1;i=6104
ns=1;i=6106
ns=1;i=6108
ns=1;i=6110
ns=1;i=6112
ns=1;i=6114
ns=1;i=6116
ns=1;i=6117
ns=1;i=6118
ns=1;i=6119
AftertreatmentState
State of the aftertreatment system.
i=80
i=63
ns=1;i=1018
DefLevel
Diesel Exhaust Fluid tank level. SAE J1939 SPN 1761. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1018
ns=1;i=6105
EngineeringUnits
i=78
i=68
ns=1;i=6104
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
DefTemperature
DEF tank temperature. SAE J1939 SPN 3031. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1018
ns=1;i=6107
EngineeringUnits
i=78
i=68
ns=1;i=6106
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
DefQuality
DEF concentration/quality. SAE J1939 SPN 3364. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1018
ns=1;i=6109
EngineeringUnits
i=78
i=68
ns=1;i=6108
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
DpfSootLoad
Diesel particulate filter soot load. SAE J1939 SPN 3719. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1018
ns=1;i=6111
EngineeringUnits
i=78
i=68
ns=1;i=6110
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
DpfAshLoad
Diesel particulate filter ash load. SAE J1939 SPN 3720. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1018
ns=1;i=6113
EngineeringUnits
i=78
i=68
ns=1;i=6112
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
ExhaustGasTemperature
Exhaust gas temperature. SAE J1939 SPN 173. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1018
ns=1;i=6115
EngineeringUnits
i=78
i=68
ns=1;i=6114
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
RegenerationRequired
A DPF regeneration is required.
i=80
i=63
ns=1;i=1018
RegenerationInhibited
DPF regeneration is currently inhibited.
i=80
i=63
ns=1;i=1018
InitiateRegeneration
Request a manual DPF regeneration.
i=80
ns=1;i=1018
InhibitRegeneration
Enable or disable the inhibit of automatic regeneration.
i=80
ns=1;i=1018
ns=1;i=6120
InputArguments
i=78
i=68
ns=1;i=6119
i=297Inhibiti=1-1TRUE to inhibit regeneration.
EngineType
The prime-mover engine of a generator set. Exposes engine telemetry, typically obtained over the CAN bus / SAE J1939 interface, and identification.
GEN-Components
ns=2;i=15063
ns=1;i=6121
ns=1;i=6123
ns=1;i=6125
ns=1;i=6127
ns=1;i=6129
ns=1;i=6131
ns=1;i=6133
ns=1;i=6135
ns=1;i=6137
ns=1;i=6139
ns=1;i=6141
ns=1;i=6143
ns=1;i=6145
ns=1;i=6147
ns=1;i=6149
ns=1;i=6150
ns=1;i=6151
ns=1;i=6153
ns=1;i=6154
ns=1;i=6156
ns=1;i=6157
Speed
Engine speed. SAE J1939 SPN 190. EngineeringUnits: rpm.
i=78
i=17497
ns=1;i=1002
ns=1;i=6122
EngineeringUnits
i=78
i=68
ns=1;i=6121
i=889http://www.opcfoundation.org/UA/units/un/cefact5394509r/minrevolutions per minute
PercentLoad
Engine percent load at current speed. SAE J1939 SPN 92. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1002
ns=1;i=6124
EngineeringUnits
i=78
i=68
ns=1;i=6123
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
PercentTorque
Actual engine percent torque. SAE J1939 SPN 513. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1002
ns=1;i=6126
EngineeringUnits
i=78
i=68
ns=1;i=6125
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
OilPressure
Engine oil pressure. SAE J1939 SPN 100. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1002
ns=1;i=6128
EngineeringUnits
i=78
i=68
ns=1;i=6127
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
OilTemperature
Engine oil temperature. SAE J1939 SPN 175. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1002
ns=1;i=6130
EngineeringUnits
i=78
i=68
ns=1;i=6129
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
CoolantTemperature
Engine coolant temperature. SAE J1939 SPN 110. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1002
ns=1;i=6132
EngineeringUnits
i=78
i=68
ns=1;i=6131
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
CoolantPressure
Engine coolant pressure. SAE J1939 SPN 109. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1002
ns=1;i=6134
EngineeringUnits
i=78
i=68
ns=1;i=6133
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
FuelRate
Engine fuel consumption rate. SAE J1939 SPN 183. EngineeringUnits: L/h.
i=80
i=17497
ns=1;i=1002
ns=1;i=6136
EngineeringUnits
i=78
i=68
ns=1;i=6135
i=889http://www.opcfoundation.org/UA/units/un/cefact4535090l/hlitre per hour
FuelTemperature
Engine fuel temperature. SAE J1939 SPN 174. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1002
ns=1;i=6138
EngineeringUnits
i=78
i=68
ns=1;i=6137
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
IntakeManifoldPressure
Intake manifold (boost) pressure. SAE J1939 SPN 102. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1002
ns=1;i=6140
EngineeringUnits
i=78
i=68
ns=1;i=6139
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
IntakeManifoldTemperature
Intake manifold temperature. SAE J1939 SPN 105. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1002
ns=1;i=6142
EngineeringUnits
i=78
i=68
ns=1;i=6141
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
ExhaustGasTemperature
Exhaust gas temperature. SAE J1939 SPN 173. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1002
ns=1;i=6144
EngineeringUnits
i=78
i=68
ns=1;i=6143
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
BarometricPressure
Ambient barometric pressure. SAE J1939 SPN 108. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1002
ns=1;i=6146
EngineeringUnits
i=78
i=68
ns=1;i=6145
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
EngineHours
Total engine run hours. SAE J1939 SPN 247. EngineeringUnits: h.
i=78
i=17497
ns=1;i=1002
ns=1;i=6148
EngineeringUnits
i=78
i=68
ns=1;i=6147
i=889http://www.opcfoundation.org/UA/units/un/cefact4740434hhour
NumberOfStarts
Total number of engine start attempts.
i=80
i=63
ns=1;i=1002
Aspiration
Air induction method of the engine.
i=80
i=63
ns=1;i=1002
Displacement
Engine displacement. EngineeringUnits: l.
i=80
i=17497
ns=1;i=1002
ns=1;i=6152
EngineeringUnits
i=78
i=68
ns=1;i=6151
i=889http://www.opcfoundation.org/UA/units/un/cefact5002322llitre
CylinderCount
Number of cylinders.
i=80
i=63
ns=1;i=1002
RatedSpeed
Rated (synchronous) engine speed, e.g. 1500 or 1800 rpm. EngineeringUnits: rpm.
i=80
i=17497
ns=1;i=1002
ns=1;i=6155
EngineeringUnits
i=78
i=68
ns=1;i=6154
i=889http://www.opcfoundation.org/UA/units/un/cefact5394509r/minrevolutions per minute
CanInterface
CAN bus / SAE J1939 diagnostic interface of the engine ECU.
i=80
ns=1;i=1010
ns=1;i=1002
Aftertreatment
Exhaust aftertreatment subsystem, when equipped.
i=80
ns=1;i=1018
ns=1;i=1002
AlternatorPhaseType
Per-phase electrical measurements of the alternator output.
GEN-Components
i=58
ns=1;i=6158
ns=1;i=6160
ns=1;i=6162
ns=1;i=6164
ns=1;i=6166
ns=1;i=6168
ns=1;i=6170
LineToNeutralVoltage
Phase (line-to-neutral) RMS voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1004
ns=1;i=6159
EngineeringUnits
i=78
i=68
ns=1;i=6158
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
LineToLineVoltage
Line-to-line RMS voltage referenced to the next phase. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1004
ns=1;i=6161
EngineeringUnits
i=78
i=68
ns=1;i=6160
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
Current
Phase RMS current. EngineeringUnits: A.
i=78
i=17497
ns=1;i=1004
ns=1;i=6163
EngineeringUnits
i=78
i=68
ns=1;i=6162
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
RealPower
Per-phase real power. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1004
ns=1;i=6165
EngineeringUnits
i=78
i=68
ns=1;i=6164
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
ReactivePower
Per-phase reactive power. EngineeringUnits: kvar.
i=80
i=17497
ns=1;i=1004
ns=1;i=6167
EngineeringUnits
i=78
i=68
ns=1;i=6166
i=889http://www.opcfoundation.org/UA/units/un/cefact4937298kvarkilovar
ApparentPower
Per-phase apparent power. EngineeringUnits: kVA.
i=80
i=17497
ns=1;i=1004
ns=1;i=6169
EngineeringUnits
i=78
i=68
ns=1;i=6168
i=889http://www.opcfoundation.org/UA/units/un/cefact4937281kV·Akilovolt ampere
PowerFactor
Per-phase power factor (-1..1).
i=80
i=63
ns=1;i=1004
AlternatorType
The alternator (generator end) that converts mechanical power into AC electrical power. Exposes aggregate and per-phase electrical measurements.
GEN-Components
ns=2;i=15063
ns=1;i=6171
ns=1;i=6173
ns=1;i=6175
ns=1;i=6177
ns=1;i=6179
ns=1;i=6181
ns=1;i=6183
ns=1;i=6185
ns=1;i=6186
ns=1;i=6188
ns=1;i=6190
ns=1;i=6192
ns=1;i=6194
ns=1;i=6196
ns=1;i=6198
ns=1;i=6200
ns=1;i=6201
ns=1;i=6202
ns=1;i=6203
ns=1;i=6205
ns=1;i=6207
ns=1;i=6208
ns=1;i=6209
Frequency
Output frequency. EngineeringUnits: Hz.
i=78
i=17497
ns=1;i=1003
ns=1;i=6172
EngineeringUnits
i=78
i=68
ns=1;i=6171
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
AverageLineToLineVoltage
Average line-to-line RMS voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1003
ns=1;i=6174
EngineeringUnits
i=78
i=68
ns=1;i=6173
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
AverageLineToNeutralVoltage
Average line-to-neutral RMS voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1003
ns=1;i=6176
EngineeringUnits
i=78
i=68
ns=1;i=6175
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
AverageCurrent
Average line RMS current. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1003
ns=1;i=6178
EngineeringUnits
i=78
i=68
ns=1;i=6177
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
TotalRealPower
Total three-phase real power. EngineeringUnits: kW.
i=78
i=17497
ns=1;i=1003
ns=1;i=6180
EngineeringUnits
i=78
i=68
ns=1;i=6179
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
TotalReactivePower
Total three-phase reactive power. EngineeringUnits: kvar.
i=80
i=17497
ns=1;i=1003
ns=1;i=6182
EngineeringUnits
i=78
i=68
ns=1;i=6181
i=889http://www.opcfoundation.org/UA/units/un/cefact4937298kvarkilovar
TotalApparentPower
Total three-phase apparent power. EngineeringUnits: kVA.
i=80
i=17497
ns=1;i=1003
ns=1;i=6184
EngineeringUnits
i=78
i=68
ns=1;i=6183
i=889http://www.opcfoundation.org/UA/units/un/cefact4937281kV·Akilovolt ampere
AveragePowerFactor
Average power factor (-1..1).
i=80
i=63
ns=1;i=1003
TotalRealEnergy
Cumulative generated real energy. EngineeringUnits: kW.h.
i=80
i=17497
ns=1;i=1003
ns=1;i=6187
EngineeringUnits
i=78
i=68
ns=1;i=6186
i=889http://www.opcfoundation.org/UA/units/un/cefact4937544kW·hkilowatt hour
LoadPercent
Output as a percentage of rated power. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1003
ns=1;i=6189
EngineeringUnits
i=78
i=68
ns=1;i=6188
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
WindingTemperature1
Stator winding temperature, phase 1. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1003
ns=1;i=6191
EngineeringUnits
i=78
i=68
ns=1;i=6190
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
WindingTemperature2
Stator winding temperature, phase 2. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1003
ns=1;i=6193
EngineeringUnits
i=78
i=68
ns=1;i=6192
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
WindingTemperature3
Stator winding temperature, phase 3. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1003
ns=1;i=6195
EngineeringUnits
i=78
i=68
ns=1;i=6194
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
BearingTemperatureDriveEnd
Drive-end bearing temperature. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1003
ns=1;i=6197
EngineeringUnits
i=78
i=68
ns=1;i=6196
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
BearingTemperatureNonDriveEnd
Non-drive-end bearing temperature. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1003
ns=1;i=6199
EngineeringUnits
i=78
i=68
ns=1;i=6198
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
Connection
Winding connection configuration.
i=80
i=63
ns=1;i=1003
ExcitationType
Excitation method.
i=80
i=63
ns=1;i=1003
NumberOfPoles
Number of alternator poles.
i=80
i=63
ns=1;i=1003
VoltageSetpoint
AVR voltage setpoint. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1003
ns=1;i=6204
EngineeringUnits
i=78
i=68
ns=1;i=6203
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
FieldCurrent
Excitation field current. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1003
ns=1;i=6206
EngineeringUnits
i=78
i=68
ns=1;i=6205
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
L1
Phase 1 (A) measurements.
i=78
ns=1;i=1004
ns=1;i=1003
L2
Phase 2 (B) measurements.
i=80
ns=1;i=1004
ns=1;i=1003
L3
Phase 3 (C) measurements.
i=80
ns=1;i=1004
ns=1;i=1003
FuelSystemType
The fuel storage and delivery subsystem of a generator set.
GEN-Components
ns=2;i=15063
ns=1;i=6210
ns=1;i=6211
ns=1;i=6213
ns=1;i=6215
ns=1;i=6217
ns=1;i=6219
ns=1;i=6221
ns=1;i=6223
ns=1;i=6225
ns=1;i=6227
FuelType
Primary fuel of the set.
i=78
i=63
ns=1;i=1005
FuelLevel
Fuel tank level. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1005
ns=1;i=6212
EngineeringUnits
i=78
i=68
ns=1;i=6211
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
FuelVolume
Usable fuel volume remaining. EngineeringUnits: l.
i=80
i=17497
ns=1;i=1005
ns=1;i=6214
EngineeringUnits
i=78
i=68
ns=1;i=6213
i=889http://www.opcfoundation.org/UA/units/un/cefact5002322llitre
FuelConsumptionRate
Fuel consumption rate. EngineeringUnits: L/h.
i=80
i=17497
ns=1;i=1005
ns=1;i=6216
EngineeringUnits
i=78
i=68
ns=1;i=6215
i=889http://www.opcfoundation.org/UA/units/un/cefact4535090l/hlitre per hour
FuelPressure
Fuel supply pressure. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1005
ns=1;i=6218
EngineeringUnits
i=78
i=68
ns=1;i=6217
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
FuelTemperature
Fuel temperature. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1005
ns=1;i=6220
EngineeringUnits
i=78
i=68
ns=1;i=6219
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
GasSupplyPressure
Gas inlet pressure for gaseous-fuel sets. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1005
ns=1;i=6222
EngineeringUnits
i=78
i=68
ns=1;i=6221
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
RuntimeRemaining
Estimated runtime remaining at current load. EngineeringUnits: h.
i=80
i=17497
ns=1;i=1005
ns=1;i=6224
EngineeringUnits
i=78
i=68
ns=1;i=6223
i=889http://www.opcfoundation.org/UA/units/un/cefact4740434hhour
TotalFuelConsumed
Cumulative fuel consumed. EngineeringUnits: l.
i=80
i=17497
ns=1;i=1005
ns=1;i=6226
EngineeringUnits
i=78
i=68
ns=1;i=6225
i=889http://www.opcfoundation.org/UA/units/un/cefact5002322llitre
WaterInFuel
Water detected in the fuel/water separator.
i=80
i=63
ns=1;i=1005
CoolingSystemType
The engine cooling subsystem of a generator set.
GEN-Components
ns=2;i=15063
ns=1;i=6228
ns=1;i=6230
ns=1;i=6232
ns=1;i=6234
ns=1;i=6235
ns=1;i=6237
ns=1;i=6238
CoolantTemperature
Engine coolant temperature. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1006
ns=1;i=6229
EngineeringUnits
i=78
i=68
ns=1;i=6228
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
CoolantLevel
Coolant level. SAE J1939 SPN 111. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1006
ns=1;i=6231
EngineeringUnits
i=78
i=68
ns=1;i=6230
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
CoolantPressure
Coolant pressure. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1006
ns=1;i=6233
EngineeringUnits
i=78
i=68
ns=1;i=6232
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
CoolingMethod
Cooling method (air- or liquid-cooled).
i=80
i=63
ns=1;i=1006
AmbientTemperature
Ambient air temperature at the set. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1006
ns=1;i=6236
EngineeringUnits
i=78
i=68
ns=1;i=6235
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
RadiatorFanRunning
The radiator fan is running.
i=80
i=63
ns=1;i=1006
JacketWaterHeaterActive
The jacket-water block heater is active.
i=80
i=63
ns=1;i=1006
LubricationSystemType
The engine lubrication subsystem of a generator set.
GEN-Components
ns=2;i=15063
ns=1;i=6239
ns=1;i=6241
ns=1;i=6243
ns=1;i=6245
OilPressure
Engine oil pressure. SAE J1939 SPN 100. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1007
ns=1;i=6240
EngineeringUnits
i=78
i=68
ns=1;i=6239
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
OilTemperature
Engine oil temperature. SAE J1939 SPN 175. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1007
ns=1;i=6242
EngineeringUnits
i=78
i=68
ns=1;i=6241
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
OilLevel
Engine oil level. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1007
ns=1;i=6244
EngineeringUnits
i=78
i=68
ns=1;i=6243
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
OilFilterDifferentialPressure
Oil filter differential pressure. EngineeringUnits: kPa.
i=80
i=17497
ns=1;i=1007
ns=1;i=6246
EngineeringUnits
i=78
i=68
ns=1;i=6245
i=889http://www.opcfoundation.org/UA/units/un/cefact4935745kPakilopascal
StartingSystemType
The starting/battery subsystem of a generator set.
GEN-Components
ns=2;i=15063
ns=1;i=6247
ns=1;i=6249
ns=1;i=6251
ns=1;i=6252
BatteryVoltage
Starting battery voltage. SAE J1939 SPN 168. EngineeringUnits: V.
i=78
i=17497
ns=1;i=1008
ns=1;i=6248
EngineeringUnits
i=78
i=68
ns=1;i=6247
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
BatteryChargingCurrent
Battery charging current. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1008
ns=1;i=6250
EngineeringUnits
i=78
i=68
ns=1;i=6249
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
BatteryChargerActive
The battery charger is active.
i=80
i=63
ns=1;i=1008
StartAttempts
Number of start attempts in the last start sequence.
i=80
i=63
ns=1;i=1008
GeneratorControllerType
The generator set control panel. Provides controller identity, mode/state visibility and remote-monitoring status.
GEN-Components
ns=2;i=15063
ns=1;i=6253
ns=1;i=6254
ns=1;i=6255
ns=1;i=6256
ns=1;i=6257
ns=1;i=6258
ns=1;i=6259
ns=1;i=6260
ns=1;i=6261
ns=1;i=6262
ns=1;i=6263
ControllerFamily
Vendor controller product family or product line.
i=80
i=68
ns=1;i=1009
FirmwareVersion
Controller firmware version.
i=80
i=68
ns=1;i=1009
ApplicationSoftwareVersion
Application software version.
i=80
i=68
ns=1;i=1009
ConfigurationVersion
Configuration/calibration version.
i=80
i=68
ns=1;i=1009
InAutoMode
The controller is in automatic mode.
i=80
i=63
ns=1;i=1009
NotInAuto
The controller is NOT in automatic mode (NFPA annunciation).
i=80
i=63
ns=1;i=1009
RemoteStartEnabled
Remote start is enabled.
i=80
i=63
ns=1;i=1009
RemoteControlEnabled
Remote control is enabled.
i=80
i=63
ns=1;i=1009
CloudConnected
Connected to the remote-monitoring cloud.
i=80
i=63
ns=1;i=1009
ModbusEnabled
The Modbus interface is enabled.
i=80
i=63
ns=1;i=1009
SignalStrength
Cellular/network signal strength. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1009
ns=1;i=6264
EngineeringUnits
i=78
i=68
ns=1;i=6263
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
GeneratorRatingType
A single nameplate power rating point of a generator set for a given application/duty (ISO 8528).
GEN-Rating
i=58
ns=1;i=6265
ns=1;i=6266
ns=1;i=6268
ns=1;i=6270
ns=1;i=6271
ns=1;i=6273
ns=1;i=6275
ns=1;i=6277
ns=1;i=6279
ns=1;i=6280
ns=1;i=6281
ns=1;i=6283
ApplicationRating
Application/duty of this rating.
i=78
i=63
ns=1;i=1012
RatedRealPower
Rated real power. EngineeringUnits: kW.
i=78
i=17497
ns=1;i=1012
ns=1;i=6267
EngineeringUnits
i=78
i=68
ns=1;i=6266
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
RatedApparentPower
Rated apparent power. EngineeringUnits: kVA.
i=80
i=17497
ns=1;i=1012
ns=1;i=6269
EngineeringUnits
i=78
i=68
ns=1;i=6268
i=889http://www.opcfoundation.org/UA/units/un/cefact4937281kV·Akilovolt ampere
RatedPowerFactor
Rated power factor.
i=80
i=63
ns=1;i=1012
RatedVoltage
Rated line-to-line voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1012
ns=1;i=6272
EngineeringUnits
i=78
i=68
ns=1;i=6271
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
RatedCurrent
Rated line current. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1012
ns=1;i=6274
EngineeringUnits
i=78
i=68
ns=1;i=6273
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
RatedFrequency
Rated frequency. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1012
ns=1;i=6276
EngineeringUnits
i=78
i=68
ns=1;i=6275
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
RatedSpeed
Rated engine speed. EngineeringUnits: rpm.
i=80
i=17497
ns=1;i=1012
ns=1;i=6278
EngineeringUnits
i=78
i=68
ns=1;i=6277
i=889http://www.opcfoundation.org/UA/units/un/cefact5394509r/minrevolutions per minute
PhaseCount
Number of phases (1 or 3).
i=80
i=68
ns=1;i=1012
Connection
Winding connection for this rating.
i=80
i=63
ns=1;i=1012
AmbientTemperature
Reference ambient temperature for the rating. EngineeringUnits: degC.
i=80
i=17497
ns=1;i=1012
ns=1;i=6282
EngineeringUnits
i=78
i=68
ns=1;i=6281
i=889http://www.opcfoundation.org/UA/units/un/cefact4408652°Cdegree Celsius
Altitude
Reference altitude for the rating. EngineeringUnits: m.
i=80
i=17497
ns=1;i=1012
ns=1;i=6284
EngineeringUnits
i=78
i=68
ns=1;i=6283
i=889http://www.opcfoundation.org/UA/units/un/cefact5067858mmetre
GeneratorProtectionAlarmType
Alarm raised by a generator protection/shutdown function. Extends OffNormalAlarmType with the protection function, severity and J1939 origin.
GEN-Alarms
i=10637
ns=1;i=6285
ns=1;i=6286
ns=1;i=6287
ns=1;i=6288
ns=1;i=6289
ns=1;i=6290
ProtectionFunction
The protection function that raised the alarm.
i=78
i=68
ns=1;i=1017
GeneratorAlarmSeverity
Severity class of the alarm.
i=80
i=68
ns=1;i=1017
IsShutdown
TRUE if the condition caused an engine shutdown.
i=80
i=68
ns=1;i=1017
Spn
SAE J1939 SPN when the alarm originates from the engine ECU.
i=80
i=68
ns=1;i=1017
Fmi
SAE J1939 FMI when the alarm originates from the engine ECU.
i=80
i=68
ns=1;i=1017
SubsystemName
Name of the originating subsystem.
i=80
i=68
ns=1;i=1017
GeneratorSetType
A generator set (GenSet): a complete electrical power generation asset composed of a prime-mover engine, an alternator, a fuel system, cooling, lubrication, starting and control subsystems. Applicable to the whole industry, from small home-standby units to house-sized multi-megawatt industrial sets.
GEN-GeneratorSet
ns=2;i=1002
ns=1;i=6291
ns=1;i=6292
ns=1;i=6295
ns=1;i=6296
ns=1;i=6297
ns=1;i=6298
ns=1;i=6299
ns=1;i=6300
ns=1;i=6301
ns=1;i=6302
ns=1;i=6303
ns=1;i=6304
ns=1;i=6305
ns=1;i=6306
ns=1;i=6307
ns=1;i=6308
ns=1;i=6309
ns=1;i=6310
ns=1;i=6311
ns=1;i=6312
ns=1;i=6314
ns=1;i=6315
ns=1;i=6316
ns=1;i=6317
ns=1;i=6318
ns=1;i=6320
ns=1;i=1017
Identification
Generator identification and nameplate (Machinery building block).
i=78
ns=1;i=1016
ns=1;i=1001
MachineryBuildingBlocks
Container for standardized Machinery building blocks.
i=80
i=61
ns=1;i=1001
ns=1;i=6293
ns=1;i=6294
MachineryItemState
Generic Machinery availability state machine (interoperability).
i=80
ns=3;i=1002
ns=1;i=6292
MachineryOperationMode
Generic Machinery operation-mode state machine (interoperability).
i=80
ns=3;i=1008
ns=1;i=6292
OperatingState
Detailed generator-set operating state machine.
i=78
ns=1;i=1011
ns=1;i=1001
OperatingMode
Selector mode of the control panel (Off/Manual/Auto/Test/...).
i=78
i=63
ns=1;i=1001
EmissionsStandard
Emissions certification standard of the set.
i=80
i=63
ns=1;i=1001
Application
Application segment, e.g. Residential, DataCenter, Healthcare, Rental, PrimePower.
i=80
i=68
ns=1;i=1001
GeneratorBreakerClosed
The generator (output) breaker is closed.
i=80
i=63
ns=1;i=1001
GeneratorBreakerAvailable
The generator breaker is available to close.
i=80
i=63
ns=1;i=1001
RemoteStartInput
The remote start input is asserted.
i=80
i=63
ns=1;i=1001
RunRequest
A run request is active from any source.
i=80
i=63
ns=1;i=1001
LoadInhibit
Loading of the set is inhibited.
i=80
i=63
ns=1;i=1001
AvailableToLoad
The set is up to speed and voltage and is ready to accept load.
i=80
i=63
ns=1;i=1001
Engine
The prime-mover engine.
i=78
ns=1;i=1002
ns=1;i=1001
Alternator
The alternator (generator end).
i=78
ns=1;i=1003
ns=1;i=1001
Controller
The control panel.
i=78
ns=1;i=1009
ns=1;i=1001
FuelSystem
The fuel subsystem.
i=80
ns=1;i=1005
ns=1;i=1001
CoolingSystem
The cooling subsystem.
i=80
ns=1;i=1006
ns=1;i=1001
LubricationSystem
The lubrication subsystem.
i=80
ns=1;i=1007
ns=1;i=1001
StartingSystem
The starting/battery subsystem.
i=80
ns=1;i=1008
ns=1;i=1001
Ratings
Nameplate power ratings of the set (e.g. Standby and Prime).
i=78
i=61
ns=1;i=1001
ns=1;i=6313
<Rating>
A nameplate rating point of the set.
i=11508
ns=1;i=1012
ns=1;i=6312
Start
Command the set to start in the current operating mode.
i=80
ns=1;i=1001
Stop
Command a normal stop (with cooldown).
i=80
ns=1;i=1001
EmergencyStop
Command an immediate emergency stop.
i=80
ns=1;i=1001
ResetFaults
Reset latched faults / lockout.
i=80
ns=1;i=1001
SetOperatingMode
Set the control-panel selector mode.
i=80
ns=1;i=1001
ns=1;i=6319
InputArguments
i=78
i=68
ns=1;i=6318
i=297Modens=1;i=3001-1The requested operating mode.
StartTest
Start a test run for a given duration.
i=80
ns=1;i=1001
ns=1;i=6321
InputArguments
i=78
i=68
ns=1;i=6320
i=297DurationMinutesi=7-1Test duration in minutes.i=297WithLoadi=1-1TRUE to run the test with load.
TransferSwitchSourceType
One power source (normal/utility or emergency/generator) of an automatic transfer switch, with its availability and measurements.
GEN-TransferSwitch
i=58
ns=1;i=6322
ns=1;i=6323
ns=1;i=6324
ns=1;i=6326
ns=1;i=6328
Available
The source is present and energized.
i=78
i=63
ns=1;i=1019
Acceptable
The source is within acceptable voltage/frequency limits.
i=80
i=63
ns=1;i=1019
Voltage
Source line-to-line voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1019
ns=1;i=6325
EngineeringUnits
i=78
i=68
ns=1;i=6324
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
Frequency
Source frequency. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1019
ns=1;i=6327
EngineeringUnits
i=78
i=68
ns=1;i=6326
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
PhaseRotation
Phase rotation of the source (e.g. ABC or CBA).
i=80
i=68
ns=1;i=1019
AutomaticTransferSwitchType
An automatic transfer switch (ATS) that transfers a load between a normal source (utility) and an emergency source (generator).
GEN-TransferSwitch
ns=2;i=1002
ns=1;i=6329
ns=1;i=6330
ns=1;i=6331
ns=1;i=6332
ns=1;i=6333
ns=1;i=6334
ns=1;i=6335
ns=1;i=6336
ns=1;i=6337
ns=1;i=6338
ns=1;i=6339
ns=1;i=6340
ns=1;i=6342
ns=1;i=6343
ns=1;i=6344
ns=1;i=6346
ns=1;i=6347
ns=1;i=6348
ns=1;i=6349
ns=1;i=6350
ns=1;i=6351
ns=1;i=6352
ns=1;i=6353
ns=1;i=6354
Identification
ATS identification and nameplate.
i=80
ns=3;i=1012
ns=1;i=1013
Position
Contact position of the switch.
i=78
i=63
ns=1;i=1013
OperatingState
Operating state of the switch.
i=80
i=63
ns=1;i=1013
TransitionType
Transition method of the switch.
i=80
i=63
ns=1;i=1013
Source1
Source 1 (normal/utility).
i=78
ns=1;i=1019
ns=1;i=1013
Source2
Source 2 (emergency/generator).
i=78
ns=1;i=1019
ns=1;i=1013
PreferredSource
The preferred source (1 = normal, 2 = emergency).
i=80
i=68
ns=1;i=1013
Source1Connected
The load is connected to Source 1.
i=80
i=63
ns=1;i=1013
Source2Connected
The load is connected to Source 2.
i=80
i=63
ns=1;i=1013
TransferInhibited
Transfer is currently inhibited.
i=80
i=63
ns=1;i=1013
TransferInhibitReason
Reason transfer is inhibited, if any.
i=80
i=68
ns=1;i=1013
RatedCurrent
Rated current of the switch. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1013
ns=1;i=6341
EngineeringUnits
i=78
i=68
ns=1;i=6340
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
PoleCount
Number of poles.
i=80
i=68
ns=1;i=1013
ServiceEntranceRated
The switch is service-entrance rated.
i=80
i=63
ns=1;i=1013
LoadCurrent
Load current through the switch. EngineeringUnits: A.
i=80
i=17497
ns=1;i=1013
ns=1;i=6345
EngineeringUnits
i=78
i=68
ns=1;i=6344
i=889http://www.opcfoundation.org/UA/units/un/cefact4279632Aampere
TransferCount
Cumulative number of transfers.
i=80
i=63
ns=1;i=1013
LastTransferTime
Timestamp of the last transfer.
i=80
i=63
ns=1;i=1013
EngineStartDelay
Engine-start (outage confirmation) delay.
i=80
i=63
ns=1;i=1013
TransferToEmergencyDelay
Delay before transferring to emergency.
i=80
i=63
ns=1;i=1013
RetransferToNormalDelay
Delay before retransferring to normal.
i=80
i=63
ns=1;i=1013
CooldownDelay
Engine cooldown (unloaded run) delay.
i=80
i=63
ns=1;i=1013
Transfer
Command a transfer to the emergency source.
i=80
ns=1;i=1013
Retransfer
Command a retransfer to the normal source.
i=80
ns=1;i=1013
InhibitTransfer
Enable or disable the transfer inhibit.
i=80
ns=1;i=1013
ns=1;i=6355
InputArguments
i=78
i=68
ns=1;i=6354
i=297Inhibiti=1-1TRUE to inhibit transfer.
ParallelingControllerType
A paralleling / switchgear controller that synchronizes and shares load among generator sets on a common bus, and optionally parallels with the utility.
GEN-Paralleling
ns=2;i=15063
ns=1;i=6356
ns=1;i=6357
ns=1;i=6359
ns=1;i=6361
ns=1;i=6363
ns=1;i=6365
ns=1;i=6367
ns=1;i=6369
ns=1;i=6371
ns=1;i=6373
ns=1;i=6374
ns=1;i=6375
ns=1;i=6377
ns=1;i=6379
ns=1;i=6381
ns=1;i=6382
ns=1;i=6383
ns=1;i=6385
ns=1;i=6387
ns=1;i=6388
SystemState
Operating state of the paralleling system.
i=78
i=63
ns=1;i=1014
BusVoltage
Common bus voltage. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1014
ns=1;i=6358
EngineeringUnits
i=78
i=68
ns=1;i=6357
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
BusFrequency
Common bus frequency. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1014
ns=1;i=6360
EngineeringUnits
i=78
i=68
ns=1;i=6359
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
TotalBusRealPower
Total real power on the bus. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1014
ns=1;i=6362
EngineeringUnits
i=78
i=68
ns=1;i=6361
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
TotalBusReactivePower
Total reactive power on the bus. EngineeringUnits: kvar.
i=80
i=17497
ns=1;i=1014
ns=1;i=6364
EngineeringUnits
i=78
i=68
ns=1;i=6363
i=889http://www.opcfoundation.org/UA/units/un/cefact4937298kvarkilovar
SynchronizationAngle
Phase angle difference during synchronizing. EngineeringUnits: deg.
i=80
i=17497
ns=1;i=1014
ns=1;i=6366
EngineeringUnits
i=78
i=68
ns=1;i=6365
i=889http://www.opcfoundation.org/UA/units/un/cefact17476°degree
SlipFrequency
Slip frequency during synchronizing. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1014
ns=1;i=6368
EngineeringUnits
i=78
i=68
ns=1;i=6367
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
VoltageDifference
Voltage difference during synchronizing. EngineeringUnits: V.
i=80
i=17497
ns=1;i=1014
ns=1;i=6370
EngineeringUnits
i=78
i=68
ns=1;i=6369
i=889http://www.opcfoundation.org/UA/units/un/cefact5655636Vvolt
FrequencyDifference
Frequency difference during synchronizing. EngineeringUnits: Hz.
i=80
i=17497
ns=1;i=1014
ns=1;i=6372
EngineeringUnits
i=78
i=68
ns=1;i=6371
i=889http://www.opcfoundation.org/UA/units/un/cefact4740186Hzhertz
SyncCheckPermissive
Synchronism-check permissive to close.
i=80
i=63
ns=1;i=1014
DeadBus
The bus is dead (de-energized).
i=80
i=63
ns=1;i=1014
LoadSharePercent
This set's share of the total bus load. EngineeringUnits: %.
i=80
i=17497
ns=1;i=1014
ns=1;i=6376
EngineeringUnits
i=78
i=68
ns=1;i=6375
i=889http://www.opcfoundation.org/UA/units/un/cefact20529%percent
AvailableCapacity
Available spare capacity on the bus. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1014
ns=1;i=6378
EngineeringUnits
i=78
i=68
ns=1;i=6377
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
SpinningReserve
Spinning reserve on the bus. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1014
ns=1;i=6380
EngineeringUnits
i=78
i=68
ns=1;i=6379
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
GeneratorBreakerClosed
The generator breaker is closed.
i=80
i=63
ns=1;i=1014
UtilityBreakerClosed
The utility breaker is closed.
i=80
i=63
ns=1;i=1014
UtilityImportPower
Power imported from the utility. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1014
ns=1;i=6384
EngineeringUnits
i=78
i=68
ns=1;i=6383
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
UtilityExportPower
Power exported to the utility. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1014
ns=1;i=6386
EngineeringUnits
i=78
i=68
ns=1;i=6385
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
ConnectToBus
Synchronize and close onto the common bus.
i=80
ns=1;i=1014
DisconnectFromBus
Soft-unload and open from the common bus.
i=80
ns=1;i=1014
GeneratorSystemType
A power-generation system aggregating one or more paralleled generator sets, an optional paralleling controller and transfer switches. Models integrated power systems such as data-center and healthcare plants.
GEN-System
i=58
ns=1;i=6389
ns=1;i=6391
ns=1;i=6392
ns=1;i=6394
ns=1;i=6395
ns=1;i=6397
ns=1;i=6399
GeneratorSets
The generator sets that make up the system.
i=78
i=61
ns=1;i=1015
ns=1;i=6390
<GeneratorSet>
A generator set participating in the system.
i=11510
ns=1;i=1001
ns=1;i=6389
ParallelingController
The paralleling/switchgear controller of the system.
i=80
ns=1;i=1014
ns=1;i=1015
TransferSwitches
The transfer switches in the system.
i=80
i=61
ns=1;i=1015
ns=1;i=6393
<TransferSwitch>
A transfer switch in the system.
i=11508
ns=1;i=1013
ns=1;i=6392
NumberOfGeneratorSets
Number of generator sets in the system.
i=80
i=63
ns=1;i=1015
TotalSystemCapacity
Total installed capacity of the system. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1015
ns=1;i=6396
EngineeringUnits
i=78
i=68
ns=1;i=6395
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
TotalSystemLoad
Total load currently served by the system. EngineeringUnits: kW.
i=80
i=17497
ns=1;i=1015
ns=1;i=6398
EngineeringUnits
i=78
i=68
ns=1;i=6397
i=889http://www.opcfoundation.org/UA/units/un/cefact4937556kWkilowatt
RedundancyScheme
Redundancy scheme, e.g. N, N+1, N+2, 2N, DistributedRedundant.
i=80
i=68
ns=1;i=1015