MrAlaskan 2d55126cb8 fix: return BadInvalidState for unlatched alarm reset (#4020)
### Summary

This PR fixes the reset status code returned for unlatched alarms and
adds a regression test that verifies `Reset` and `Reset2` both report
`BadInvalidState` when the alarm is not latched.

### Problem

According to the alarm reset semantics described in OPC UA Part 9,
`Reset` is only valid for a latched alarm that is no longer active and
has already been acknowledged and confirmed when those states are
present. For any other invalid state, the server should return
`Bad_InvalidState`.

Previously, `AlarmConditionState.HandleResetCore()` returned
`BadConditionNotShelved` when `LatchedState.Id == false`. That status
code belongs to the shelving state machine, not the latched alarm reset
flow. As a result, clients calling `AlarmClient.ResetAsync()` could
receive a shelving-related error for a reset precondition failure, which
misrepresents the actual alarm state and breaks the expected Part 9
semantics.

### Changes

- Change the unlatched branch in `AlarmConditionState.HandleResetCore()`
to return `BadInvalidState` instead of `BadConditionNotShelved`.
- Add a regression test in `AlarmConditionStateMethodTests` that covers
both `Reset` and `Reset2` when `LatchedState` exists but the alarm is
not latched.