Marc SchierandCopilot ca89ac85a7 Add a Generators companion-spec sample and compose servers at a site level (#4180)
# Description

Adds a **Generators companion-specification sample** alongside the
existing pump sample, and a **`SiteCompositionServer`** that composes
several device servers into one OpenUSD scene at a supervisory level —
demonstrating that servers can be aggregated without mirroring their
address spaces.

Three things, in dependency order:

### 1. `GeneratorServer`

A self-contained server realising the draft Generators spec
(`http://opcfoundation.org/UA/Generators/`) end to end: N simulated
generating sets, DI + Machinery integration, a twelve-state operating
state machine, four protection alarms per set, six control methods, and
a per-set OpenUSD twin.

The organising idea is that **load fraction is the only independent
variable**. Everything else is a function of it:

```
V̇_f(x) = 3.67 + 100·x                fuel rate      [L/h]
η(x)   = P(x) / (V̇_f(x) · ρ · LHV)   efficiency
S = P / PF     I = S / (√3·V_LL)     f = N·p / 120
```

This is not stylistic. When each measurement is an independent
oscillator — as the pump sample's simulation once was — a server happily
publishes a duty point no real machine could occupy, and no test can
catch it because there is nothing for the values to be inconsistent
*with*. Deriving them from one variable means `P = √3·V·I·PF` and `η =
P/(V̇·ρ·LHV)` hold at every tick by construction. The published
`DATASHEET.md`, the engineering ranges, the trip points and the
simulation all read the same constants in `GeneratorDatasheet.cs`, so
the document and the server cannot describe different machines.

The machine is a fictitious **SimGen Systems GenX-500** (400 kW prime /
440 kW standby, 400/230 V, 50 Hz, four-pole). Figures are representative
of a real industrial genset class; no vendor is named anywhere in the
code or docs.

### 2. Cross-server composition in the connector

`RemoteSessionFactory` already existed in the client library but the
connector CLI never set it, so cross-server composition was unreachable.
`--federate` wires it up: the connector opens a session to each server
named by a component binding, discovers its representations and drives
its bindings into the same stage.

It is **opt-in** because the endpoint the connector dials comes from the
server being rendered rather than from the operator, which makes
honouring it a trust decision. Federation is best-effort per component —
a subordinate that is down is logged and skipped, and the rest of the
scene still renders — which is the only `src/` change in this PR.

### 3. `SiteCompositionServer`

Owns no devices. It publishes a site stage plus one cross-server
component binding per subordinate, carrying that server's
`ComponentServerUri` and `ComponentEndpointUrl`. Nothing is mirrored, so
there is no cache to invalidate and no second copy of the truth.

## Notes for reviewers

**Everything interesting in this PR was found by running the servers,
not by reading the code.** Six defects, none of which looked wrong in
review:

- `IsShutdown` and `SubsystemName` are *optional* on
`GeneratorProtectionAlarmType`, so the generated factory does not
materialise them. `CreateOrReplace` alone produces a child that exists,
appears in `GetChildren` and holds the right value — but carries **no
`ReferenceTypeId`**, so no browse can reach it. Every alarm was
publishing its trip without saying whether the trip stops the machine or
which subsystem to go to. `AddXxx(context)` first is what gives the
child its `HasProperty` reference.
- **The protections could never fire.** Every trip point sits outside
the band the datasheet curves produce — that is what a datasheet *means*
— so all four alarms, the shutdown class, `ResetFaults` and the whole
`Fault` branch of the state machine were unreachable while the README
documented them as observable. Overload was worse: the load clamp
ceiling was set to exactly the trip point, making a
strictly-greater-than comparison unsatisfiable. Faults are now
injectable, and the first set — the one the hero camera frames —
develops one on a slow rotation.
- **A shutdown trip removes the condition that caused it**, because oil
pressure and coolant temperature are only supervised while the engine
turns. Each alarm went active for one tick and cleared, leaving an
operator with a stopped machine and no indication of why. Shutdown-class
alarms now latch until the set leaves the shutdown state. Every unit
test that checked the *condition* passed throughout — the defect only
appears when the trip and the supervision interact over time.
- **`Synchronizing` and `Paralleled` were declared, drawn in the README
and never entered.** The first set now energises a dead bus and closes
onto it while every other set synchronises to a live one — both how a
real plant parallels, and what makes the two states observable.
- **The tick raced client method calls.** The simulation tick runs on a
thread-pool thread while method calls arrive on request threads, and
both transition sets and write the same nodes. A tick moving a set to
`Cooldown` and a concurrent `EmergencyStop` could interleave the paired
`CurrentState` / `CurrentState.Id` writes and leave a client with a
state *name* from one transition and a state *node* from the other — the
exact failure the paired write exists to prevent, reintroduced by the
threading model. Both paths now take one gate.
- Low oil pressure supervised from raw speed **tripped every set during
cranking**, because pressure has not built yet. Now gated on
`IsSpinning`, which is what a real start-up bypass does.

Smaller fixes: shutdown trips are applied after the whole evaluation
pass (stopping mid-loop made the remaining conditions read healthy,
collapsing simultaneous trips to whichever came first in the table);
`ResetFaults` reports its clears as events (a client learns of condition
state changes only through events, so a silent clear leaves an
alarm-list client showing it forever); the start counter moved into the
transition so commanded starts are counted; the federated connector
closes the remote session if the connector constructor throws between
taking ownership and registering it; and `prepare_machinery_nodeset.py`
now *asserts* the IA namespace is last before removing it rather than
only claiming so in its docstring — removing any earlier entry would
silently renumber every namespace after it and rebind their NodeIds.

**A model limitation is left visible rather than papered over.**
`GeneratorStateMachineType` declares an emergency stop only out of
`Running`, `Loaded` and `Paralleled`, so the sample refuses
`EmergencyStop` from `Starting` and `Warmup`. A real panel stops from
anywhere. That is the specification's shape, not this sample's choice,
so it is pinned by a test and named in the docs.

**`Model/` vendors a reduced Machinery nodeset**, derived mechanically
by whitelist. The full official nodeset does not survive the model
source generator (`MODELGEN003`) and drags in IA through a single
optional `Stacklight` member a generating set does not have. Deriving it
by script keeps the provenance checkable; the whitelist is the only
thing to edit when more types are needed. **Never hand-edit the
generated output.**

**The federated scene renders end to end.** Getting there surfaced three
more defects, all of which produced a plausible-looking scene with
nothing in it: the generator sample's plant aggregation was created
under an already-registered `DeviceSet` and so was invisible to every
client (it had *never* rendered geometry, standalone or federated); the
connector's asset fetch ran on the primary session only, so composition
referenced layers that were never downloaded; and both generator colour
bindings wrote `primvars:displayColor` to prims that did not declare it,
so the renderer rejected every update while the file still looked
correct. Cross-server components compose under the subordinate's own
root, so the site layer now *places* `/Plant` and `/Powerhouse` rather
than leaving them stacked on the origin.

**`OpenUsdRepresentation` is now mounted with `HasAddIn`, not
`HasComponent`** (review feedback). The nodeset says so explicitly —
*"Mounted with HasAddIn"* — but every server in the tree used plain
`HasComponent`. It survived because `HasAddIn` is a *subtype* of
`HasComponent`: the representation still browses, still aggregates and
still drives a twin, so every functional test passed before the fix and
after it, and only a conformance checker could tell. Seven mount sites
corrected. `PumpDeviceIntegrationServer` and `MinimalRobotServer` had
hand-rolled the mount instead of calling the shared
`CreateRepresentation` helper, which is exactly how they drifted from
it. Both sample E2E suites now assert the reference type across
**every** discovered representation — a narrower check would have missed
the plant-level representation that arrived later from master still
carrying `HasComponent`.

**Live colour is not achievable in the current OpenUSD viewer, and that
is now documented rather than worked around.** Proven with a standalone
probe: `primvars:displayColor` resolves as `color3f[]` from the
`UsdGeomGprim` schema whatever the layer declares, and the `OpenUsd
0.4.0-alpha` managed API has no writer for that type. Bound
`UsdPreviewSurface` materials are not shaded either, so geometry renders
grey unless it also carries an explicit `displayColor` primvar. The
**visibility** bindings carry no such caveat and are what the samples
rely on to show state. Filed upstream as
[openusd-dotnet#2](https://github.com/marcschier/openusd-dotnet/issues/2),
[#3](https://github.com/marcschier/openusd-dotnet/issues/3) and
[#4](https://github.com/marcschier/openusd-dotnet/issues/4), and linked
from `docs/OpenUsd.md` so a reader can check whether they have since
been fixed.

## Related Issues

No tracking issue — this is additive sample and documentation work with
a single small, self-contained change to `src/` (per-component error
isolation and session-ownership hardening in
`OpenUsdConnector.Composition.cs`). Happy to open one if maintainers
would prefer it tracked.

## Checklist

- [x] I have signed the
[CLA](https://opcfoundation.org/license/cla/ContributorLicenseAgreementv1.0.pdf)
and read the
[CONTRIBUTING](https://github.com/OPCFoundation/UA-.NETStandard/blob/master/CONTRIBUTING.md)
doc.
- [x] I have added tests that prove my fix is effective or that my
feature works and increased code coverage.
- [x] I have added all necessary documentation.
- [x] I have verified that my changes do not introduce (new) build or
analyzer warnings.
- [x] I ran **all** tests locally using the **UA.slnx** solution against
at least .net **framework** and .net **10**, and all passed.
- [ ] I fixed **all** failing and flaky tests in the CI pipelines and
**all** CodeQL warnings.
- [ ] I have addressed **all** PR feedback received.

### Testing

The generator fixtures live in `tests/Opc.Ua.OpenUsd.Tests/Generator` —
**82 tests**, no new project. `Opc.Ua.Di.Tests` would have been the
natural home next to the pump fixtures, but both device samples
source-generate their own reduced `Opc.Ua.Machinery` model and expose it
via `InternalsVisibleTo`, so referencing both from one assembly makes
every Machinery type ambiguous (CS0433); `Opc.Ua.OpenUsd.Tests`
references no other sample and already hosts `RobotAssetContractTests`.
The suite runs **870** on net10.0 and net48 (784 existing + 86) and
**788** on net472, where the sample does not exist and only the
framework-independent asset-contract tests run — forgetting exactly that
exclusion broke CI on the sibling pump PR.

The tests target the things in this sample that fail *quietly*:

- **Datasheet conformance** holds the model to its own claim — rated
speed is `120·f/p`, rated current follows from the rating, the fuel
curve reproduces the published table, and `η = P/(V̇·ρ·LHV)` reconciles
at every load. Efficiency is swept across the whole simulated range to
show it stays inside (0,100) and rises monotonically; a fit that goes
negative somewhere in its range is a coincidence that happens to look
right at the duty point, not a model. A further test reads
`DATASHEET.md` and checks the document quotes the figures the server
actually serves.
- **Drift between the two descriptions of the state machine** — the
physics' `IsLegalTransition` and the model's `GeneratorStateMap` — is
checked in *both* directions. A transition the physics permits but the
map lacks moves a machine without telling a client; one the map holds
but the physics refuses is dead weight that looks supported.
- **Reachability at run time**, not just in the declared table — the
test that catches states the model declares and nothing ever enters.
- **That every protection can actually fire**, which is the half of the
alarm contract that "a healthy set annunciates nothing" does not cover.

A **hosted end-to-end fixture** connects a real client and asserts what
the address space actually exposes — the aggregation at
`/Powerhouse/Generators`, its component binding, and every per-set twin.
That is the only kind of test that catches the registration defect
above: the node object had the right browse name, binding and asset
reference, so every test that inspected objects passed while no client
could see it.

**Every state-machine and protection fix was checked by mutation.**
Restoring the clamp ceiling, the direct `Running → Loaded` path, the old
start-counter placement, or removing the alarm opt-in each makes the
corresponding test fail, naming the specific defect. A test that has
never been seen to fail has not been shown to work.

Verified against a running plant: `Synchronizing`, `Paralleled` and
`Fault` all observed on a two-set server, with
`HighCoolantTemperatureAlarm` seen active on the fault subject. Method
behaviour verified separately — per-set distinct `CurrentState` nodes,
`EmergencyStop` → `EmergencyStopped` with `Start` then refused as
`BadInvalidState`, `ResetFaults` → `Off`, `SetOperatingMode(9999)`
refused with the mode unchanged, and the other sets untouched
throughout. Also verified as a three-server federated stage.

0 warnings on a clean Release rebuild of both samples, the client
library, the connector and the tests, across every TFM.

---------

Co-authored-by: Copilot <223556219+Copilot@users.noreply.github.com>
Copilot-Session: fe608993-f3c9-4779-a6b9-9a9eabfc24ba
2026-08-07 10:48:02 +02:00
2020-05-15 19:41:55 +02:00
2021-07-26 10:06:51 +03:00

OPC UA .NET Standard Stack

Release NuGet Downloads Build Tests Coverage

🆕 This is version 2.0 of the OPC UA .NET Standard Stack (current master).

Looking for the supported 1.x release? It lives on the master378 branch (last release: 1.5.378). All new feature work happens here on master; master378 continues to receive security and critical-bug fixes for the 1.x line.

The official OPC Foundation reference implementation of OPC UA for .NET — a certified, cross-platform stack with client, server, PubSub, GDS, complex types, and source-generated tooling. Used in production across industrial control, manufacturing, energy, and IoT systems.

📦 What it is

  • A full-stack OPC UA implementation — Core / Client / Server / PubSub / GDS / LDS / Complex Types / Device Integration / Positioning libraries built on .NET, with UA-TCP and HTTPS transports.
  • Cross-platform — runs on .NET 10, .NET 9, .NET 8 (LTS), .NET Framework 4.8, and .NET Standard 2.1; ships Native-AOT-friendly assemblies.
  • Certified for compliance — the reference server has been certified through an OPC Foundation Certification Test Lab and is continuously verified against the latest Compliance Test Tool (CTT).
  • Companion-spec coverage — Part 9 (Alarms & Conditions), Part 11 (Historical Access), Part 13 (Aggregates), Part 16 (State Machines), Part 17 (Alias Names), Part 18 (Role Management), Part 20 (File Transfer), Part 100 (Device Integration), Parts 210/211 (Relative Spatial Location and Global Positioning), OPC-10030 (ISA-95 Common Model) with OPC-10031-4 Job Control V1/V2, OPC 10100-1 (WoT Connectivity), OPC 40001-1 (Industrial Automation), OPC 40010-1 (Robotics).
  • Modern developer surface — first-class Microsoft.Extensions.DependencyInjection hosting (services.AddOpcUa()), fluent server + client builders, source-generated NodeManagers and DataTypes, and an MCP server so LLMs / Copilot can drive an OPC UA client.

For the full feature breakdown see OPC UA Profiles and Facets and the What's New in 2.0 tour.

🚀 Getting started

You need the .NET 10 SDK to build the repo. From the repository root:

dotnet restore UA.slnx
dotnet build UA.slnx

For the supported target frameworks and platform notes see the Developer Guide. The official NuGet packages are published to nuget.org under the OPCFoundation.NetStandard prefix — the meta package OPCFoundation.NetStandard.Opc.Ua pulls in everything, or pick the split OPCFoundation.NetStandard.Opc.Ua.Core / .Client / .Server / .Bindings.Https packages directly. Preview builds for every successful master build are available in the Azure DevOps opcua-preview feed.

Sample applications

Each sample has its own README.md with build and run instructions.

Reference applications

PubSub samples

  • Console Reference PubSub Client — one executable with publisher, subscriber, and external (external-server adapter) modes across the supported transport profiles.

Minimal / Device-Integration samples

  • Minimal Calc Server — minimal server built on the source-generated NodeManager pipeline (Calc model).
  • Minimal Boiler Server — minimal Boiler-model server with the fluent state-machine builder; Native-AOT publishable.
  • Pump Device Integration Server — minimal Device Integration (Part 100) server using Opc.Ua.Di.Server's fluent builder.
  • Minimal Robot Server — OPC 40010 Robotics with independently configurable RSL/GPOS motion and live OpenUSD transforms.
  • Minimal ISA-95 Server — minimal server hosting the OPC-10030 ISA-95 Common Model together with OPC-10031-4 Job Control V1 and V2, using the typed common-model builder and the in-memory Job Control provider.

More sample projects are maintained in the companion OPC UA .NET Samples repository.

Developer tools

  • OPC UA MCP Server — installable .NET tool and container that exposes OPC UA client operations as MCP tools for LLMs and Copilot.

🔧 Migrating from 1.5.378 to 2.0

The 2.0 release introduces breaking API changes, and comes with a full prescriptive migration guide that links to per-area documentation covering telemetry, packages, source generation, types, encoders, node states, identity, certificates, configuration, sessions / subscriptions, alarms / model change, and TimeProvider.

Most of the mechanical migration work is automated:

  • OPCFoundation.NetStandard.Opc.Ua.MigrationAnalyzer NuGet — install it in your project to get analyzer warnings (UA0001–UA0022)
    • one-click code fixes for the patterns in the guide. Setup steps are in the package's NugetREADME.md.
  • Migration agent skill — the opcua-v20-migration skill walks Copilot / Claude / any coding agent through installing the NuGet, running dotnet format analyzers to apply auto-fixes, and handling the small residual manual patterns. The skill knows which sub-doc to load for each symptom so it stays context-efficient.

If you are still on 1.x and not ready to upgrade, stay on the master378 branch — it continues to receive security and critical-bug fixes.

🤝 Contributing and license

Community contributions are welcome. Fork the repository, make your changes on a branch, and open a pull request; see CONTRIBUTING.md for the contribution workflow.

Contributors must sign the OPC Foundation Contributor License Agreement (CLA). The CLA "I AGREE" gate is presented automatically on your first PR.

The project is licensed under the OPC Foundation MIT License. Report security vulnerabilities via the process documented in SECURITY.md.

📚 Further reading

S
Description
OPC Unified Architecture .NET Standard
Readme
290 MiB
Languages
C# 99.4%
PowerShell 0.2%